6.11 Sleep mode with ventilation level 0

For ventilation units on RLS 45 O:
Function not available.
For ventilation units on RLS 45 K, DS 45 RC:
Function available.
All ventilation units connected to a room air
control are switched off for 60 minutes (para-
meter can be adjusted). For details of opera-
tion  Chapter 2.
Sleep mode can also be switched on/off using
an optional button connected to the 230 V
input of the RLS 45 K control. The 230 VAC
input must be set to the sleep mode function
 Commissioning software.
Sleep mode is not available for ventila-
i
tion units connected to the power units.
If any key on the control is pressed during
sleep mode, the ventilation units switch back
to the ventilation level used previously.
6.12 Intermittent ventilation with ventila-
tion level 5
For ventilation units on RLS 45 O:
Function not available.
For ventilation units on RLS 45 K, DS 45 RC:
Function available.
All ventilation units connected to a room air con-
trol run for 30 minutes (parameter can be
adjusted) at ventilation level 5 (intensive ven-
tilation). For details of operation  Chapter 2.
Intermittent ventilation can also be activated
with an optional button connected to the 230
V input of the RLS 45 K control. The 230 VAC
input must be set to the intermittent ventilation
function  Commissioning software.
The intermittent ventilation is not
i
available for ventilation units
connected to the power units.
If any key on the control is pressed during
intermittent ventilation, the ventilation units
switch back to the ventilation level used
previously.
6 Operating ventilation unit(s) | UK

6.13 External OFF function

For ventilation units on RLS 45 O, DS 45 RC:
Function not available.
For ventilation units on RLS 45 K:
Function available.
This function can be used to switch off all the
ventilation system's ventilation units.
The External OFF function is switched
i
using an optional, central on/off switch
connected to the control's 230 V input.
The switch must be registered for the
External OFF function when in service
mode, parameter 230 V AC input 
Commissioning instructions.
The External OFF function impacts on
i
all the components integrated in the
ventilation system.
With RLS 45 K+PP 45 EO combinations,
i
the External Off function is also carried
out by the PP 45 RC units integrated
via the PP 45 EO.
6.14 Volumetric flow compensation in
supply air mode for exhaust air units
(e. g. ER.../ECA...)
For ventilation units on RLS 45 O, DS 45 RC:
Function not available.
For ventilation units on RLS 45 K:
Function for PP 45 O/K or PPB30 O units if
they are jointly connected to the fan interface
(Fan1/Fan2).
Use this function for the ER/ECA com-
i
bination of exhaust air fans with pure
PP 45 systems or ER/ECA combina-
tions with PPB 30 O units.
Only single-type PP 45 or PPB 30 O
i
systems are permitted at the fan inter-
face (Fan1/Fan2) of the RLS 45 K.
The "Supply air mode for exhaust air
i
units" function is only available when
using the PP 45 Act together with
PP 45 RC units.
45