4.7

Configuring the bypass settings

Automatic bypass: By default, a switch to the bypass mode will be
forced if an overload occurs. You can disable the setting.
1. Press the
options.
BYPASS".
2. Select "ENABLED" or "DISABLED" and press the
for at least one second to confirm.
3. Press the
The following settings are additionally available for configuring the
bypass mode:
Bypass voltage low limit: By default, switching to bypass mode is
disabled if the measured bypass voltage lies below 184 V. You can
specify the settings for a different voltage value.
Bypass voltage high limit: By default, switching to bypass mode is
disabled if the measured bypass voltage lies above 264 V. You can
specify the settings for a different voltage value.
Bypass frequency low limit: By default, switching to bypass mode
is disabled if the measured bypass frequency lies 10% below the
nominal frequency. You can specify the setting for a different per-
centage value.
Bypass frequency high limit: By default, switching to bypass mode
is disabled if the measured bypass frequency lies 10% above the
measured nominal frequency. You can specify the setting for a dif-
ferent percentage value.
XS6000+XS10000_manual_ger_eng_it_V1.1.2.doc
button for at least one second to enable the menu
Select
"SETTINGS"
button briefly to return to the start screen.
110 / 216
and
then
"AUTOMATIC
button
R. Kistler

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Xs10000

Inhaltsverzeichnis