of the door.
2. Keep at least a distance of 80 cm between the stove and combustible objects such as curtains, wooden
objects (cupboards and paintings) and glass objects. Keep the same distance from the flue tube.
3. Wooden construction parts within the radiation range of the stove (80 cm from the exterior of the stove)
must be covered with fireproof material.
4. If the flue tube goes through a ceiling and/or roof that consist of flammable materials, the ceiling and the
roof must be covered with fireproof materials all around (about 80 cm). Pay also attention to joisted floor
layers and any electric wiring.
5. Keep a distance of at least 50 cm (in all directions) between the stove and supporting steel construction
parts.
6. Shield off all combustible materials within a radius of 80 cm from the stove openings with non-combustible
materials.
7. Never cover the chimney breast with combustible material (e.g. paper covering).
8. The wall behind the stove must consist of, or be insulated with, fire-proof materials. The insulation material
must resist a temperature of 700 °C and have a density of 80 kg/m3. Please see for insulation materials
table page 29).
9. Avoid heat transmission when placing the stove. Heat transmission of a burning stove can penetrate the
wall and even cause fire damage on the other side of the wall. Prevention is better than cure.

Installation

The Square is tested in accordance with the international EN 13229 standardization, and has an extra additional
standardization for optimally environment-friendly heating devices related to flue gases (Section 15a B-Vg.
Des BmfWA). The stove can be connected to a flue tube to which several stoves are connected. The flue tube
has a diameter of 150 mm.

Supply of combustion air

The stove must have enough supply of fresh combustion air. If necessary, make an extra air supply opening as
close to the stove as possible to avoid draught. An extra opening for air supply is always required if:
the space has a heat recovery system.
the space has a central exhaust system.
there is a cooker hood in the same space.
The air supply opening must be closable if it goes through a fire-resistant wall. When there are several
combustion devices in the same space there must be enough air openings to guarantee proper combustion.

External air supply (optional)

External air supply is possible by installing the optional air kit (OND.SQ.6013) (See page 67).

Fans (optional)

The fans can't be placed after the stove has
been installed. When fans were ordered
they need to be installed before the stove
is built in. Always connect the fans to an
earthed wall socket. Moreover there must
be the possibility to disconnect the stove
from the electricity supply any service or
maintenance.
When starting the fans, they will start with their fastest speed, you can regulate the speed of the fans with the
knob on the left side. Please be aware that the fans will produce noise. All efforts are made to reduce this noise
as much as possible.
When refuelling the stove it's advised to turn the fans off preventing the smoke from being drawn out
!
of the stove.