9. Application as per VdS
- The temperature sensor for the power supply must be fixed to the battery.
- The power supply must be installed in a metal housing.
- The battery must be fixed using Dual lock fasteners (Item no. 055280).
10. Installation guidelines
When mounted in a separate housing the BUS connecting cable must be a shielded, twisted pair line. Wires must
correspond with the diagram below.
Keep the shield connections as short as possible to avoid the risk of a short circuit.

11. Technical data

Rated operating voltage
Operating voltage range
Frequency
Power consumption
Maximum constant current
Short-term continuous current drain (5 min.)
Maximum charging current
Approved accum. capacity as per VdS
No. of connectible accumulators
Possible accumulator combinations
Current consumption as per VdS at 52 Ah accumulator capacity:
for 60 hours, Power failure delayed < 1 min.
for 61 hours, Power failure delayed 1 hour.
Current consumption of power supply on accum. operation
Permanent accumulator monitoring
Temperature-guided accum. charging voltage
Operating temperature range
Storage temperature range
Environmental Class as per VdS
PCB dimensions (W x H x D)
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
Mounting and Connection Instructions Mains/charger unit 12 V DC / 52 Ah
Panel MB-Secure
BUS connection
+12 V DC
0 V
B
A / Data
Shield
The shield must be connected in the panel
P00225-10-002-02
2014-07-07
© 2014 Novar GmbH
BUS-2
100 V to 240 V AC
95 V to 265 V AC
50 Hz to 60 Hz
typ. 90 W / 190 VA
3 A
3.5 A max. (with charged accum.)
2.6 A
52 Ah max.
2 max.
e.g. 2x10 / 2x16 / 2x24 / 2x26 / 1x38 Ah
approx. 755 mA
approx. 742 mA
105 mA
present
present
-5 °C to +45 °C
-25 °C to +70 °C
II
92.5 x 215 x 51 mm
Mains/charger unit
+12 V DC
0 V
B
BUS-2/A (Data)