Mounting and Connection Instructions
Mains/charger unit 12 V DC / 52 Ah
Item no. 013960
1. General
Fully electronic mains/charger unit.
- Voltage-stabilized, current limited
- Redundancy standby operation
- Deep-discharging protection
- Charging circuit monitoring
- Recognition of defective batteries
- Accumulator capacity up to max. 52 Ah
- Complies with EN 50131-6
When selecting the size of housing, pay attention to the
space required for the accumulator.
2.

Operating modes - overview

The Mains/charger unit is suitable for following panels and
systems. According to the application, the type of operating
mode must be selected by jumpers.
2.1
Use in MB-Panels ( MB-Panel Mode)
Suitable for control panels 561-MB. No BUS-2 operation. Fault
messages are transmitted via output ST2. Observe chapter 7.2
to select fault messages!
2.2
Use in MB-Secure Panel
(
Bus operation mode MB-Secure)
è
Suitable for control panels MB-Secure.
Fault messages are transmitted via BUS-2.
The digital input SE (LOW active) can be freely used when operating in
"Bus operation mode MB-Secure".
2.3
Use in ACS-8 / ACS-2 plus controller
(
è
MB-Panel Mode)
Suitable for ACS-8 and ACS-2 plus
access control systems.
When installing the mains/charger
unit remove the specified bolt
of the bottom plate of the ACS-8 /
ACS-2 plus housing.
P00225-10-002-02
2014-07-07
è
G114024
3. VdS guidelines for power supply
The power supply must be connected to the mains with a
separate fuse.
If the electrical installation has an earth-leakage circuit breaker
(Fl switch), the energy supply must have its own earth-leakage
circuit breaker. The fuse and Fl switch should, if possible, be
within the security zone.
If the energy supply is not part of the control panel, it must be
installed in the immediate vicinity (without a space between) so
that an attack on the connection line is impossible without
causing mechanical damage to the housing.
The control panel and power supply should, if possible, be
screwed together.
Users not belonging to the system should not be connected to
the mains voltage.
The accumulators used in the power supply must be
approved. For parallel switching, only accumulators of the
same age and from the same production series are allowed
to be used.
The accumulators must be fixed on the housing base using
Dual lock fasteners (Item no. 055280).
4. Mounting
Attention
Safety instructions
When performing installation work of any kind, the unit must
be de-energized.
Danger - risk of electric shock!
After switching off the power supply wait at least 20 seconds
before starting work due to the internal voltages have
reduced to a safe value.
When installing the power unit in a control panel housing or
equivalent, ensure that the supplied insulating foil has been
inserted between the housing base and the underside of
the PCB. Note, that the power unit is screwed tight to the
housing base.
The non-fused earth conductor from the electric power circuit
must be connected in the immediate vicinity of the connection
terminals of the supply voltage.
The power supply line must be fixed when connecting so that
the clearance (4 mm) and creep paths (6.4 mm) between
the electronic modules and/or their periphery and the power
supply line are not shorter than stipulated.
If the neutral line cannot be clearly identified, a second pro-
tection must be available in the electric power circuit so that
2-pole separation from the electric circuit is possible.