4. Errors
Error Code
1
Detection of this error is disabled if High Temperature Alarm is set off.
2
Detection of this error is disabled in Voltage Free Mode.
3
Unit is not active when supply voltage is below approx. 190 Vac.
All alarms are on the same alarm relay.
An alarm will clear automatically as soon as the error condition is gone.
There is no need to reset; all settings are maintained.
If multiple alarms are active, the alarms are shown with the following priority:
(Highest),
14
Description
Short Circuit Sensor
(or very low resistance)
Open Circuit Sensor
Low Temperature
Threshold Alarm
High Temperature
Threshold Alarm
Output Voltage Error
Supply below 207 Vac.
,
,
Remedy
Replace sensor
Connect sensor cable or
replace sensor
Verify heating system &
sensor fixation
1
Verify heating system
2
Relay or triac malfunction /
replace unit
3
Verify supply voltage
,
,
(Lowest)