Measurements
3.9 RCD
Set function
b
Set sub-function
- C ontact voltage measurement (UC)
(test without measurement)
- T ripping time measurement (RCDt)
- Tripping current measurement
(RCD )
- R CD autotest (AUTO)
d
Connection diagram
e
Press the
f
View results and press the MEM key to save them
Displayed results:
U
: Contact voltage
C
R
: Fault loop resi-
L
stance
c
- L imit contact voltage [25 V, 50 V]
- Nominal differential RCD tripping
current
[10 mA ÷ 1000 mA]
- Multiplier of nominal differential
RCD tripping [x½, x1, x2, x5]
- Test current starting polarity and
RCD type [
Note:
Type AC
G general, non-delayed,
S selective, time-delayed,
key
Displayed results:
t:
Trip-out time
U
: Contact voltage
C
Set parameters and limits
G,
G,
S,
G,
G,
S,
G,
G,
S,
S]
, type A
positive start polarity,
negative start polarity
Displayed results:
I
:
Trip-out current
U
: Contact voltage
CI
tI:
Trip-out time
26
S,
S,
, type B
,
Displayed results:
U
:
Contact voltage
C
t1-t6: Trip-out times
RCD