Für den "Timeout des Empfangstelegramms" gelten folgende Zeiten
BAUD = 115200:
Receive_Conditions.END.RCVTIME := 25;
Receive_Conditions.END.MSGTIME := 25;
ELSIF BAUD = 57600 THEN
Receive_Conditions.END.RCVTIME := 29;
Receive_Conditions.END.MSGTIME := 29;
ELSIF BAUD = 38400 THEN
Receive_Conditions.END.RCVTIME := 33;
Receive_Conditions.END.MSGTIME := 33;
ELSIF BAUD = 19200 THEN
Receive_Conditions.END.RCVTIME := 56;
Receive_Conditions.END.MSGTIME := 56;
ELSIF BAUD = 9600 THEN
Receive_Conditions.END.RCVTIME := 72;
Receive_Conditions.END.MSGTIME := 72;
ELSIF BAUD = 4800 THEN
Receive_Conditions.END.RCVTIME := 100;
Receive_Conditions.END.MSGTIME := 124;
ELSIF BAUD = 2400 THEN
Receive_Conditions.END.RCVTIME := 100;
Receive_Conditions.END.MSGTIME := 240;
ELSIF BAUD = 1200 THEN
Receive_Conditions.END.RCVTIME := 100;
Beispiel:
5 Antriebe
Datenübertragungsrate = 9600 Bit/s
28 Zeichen pro Telegramm
Zykluszeit = 0.020 Sek
Zeitabstand = (5 * 5 * 0.02 Sek + 2 * 28 * 11 / 1200 Sek) * 3 = 1,69 Sek
Die Zeitüberwachung des Antriebs muss in diesem Fall auf ca. 2 Sekunden eingestellt