APPENDIX 2 : ALARM LIST

Description écran
Code
ALU02
Regulation probe(s) missing
ALA01
Discharge temperature probe broken or disconnected
ALA02
Gascooler pressure probe broken or disconnected
ALA03
External temperature probe broken or disconnected
ALA04
General function probe A in board 1 broken or disconnected
ALA05
General function probe B in board 1 broken or disconnected
General function probe C in board 1 broken or disconnected
ALA06
General function probe D in board 1 broken or disconnected
ALA07
General function probe E in board 1 broken or disconnected
ALA08
ALA24
Suction pressure probe broken or disconnected
ALA25
Suction temperature probe broken or disconnected
ALA43
Gascooler outlet temperature probe broken or disconected
ALB01
Low common suction pressure by pressostat Num.autom.reset: / in min
ALB02
High common condensing pressure by pressostat
ALB03
Low gascooler pressure alarm
ALB04
High gascooler pressure alarm
ALB07
Fans common overload
ALB15
High suction pressure alarm
ALB16
Low suction pressure alarm
ALC01
Alarm 1 compressor 1
ALC02
Alarm 2 compressor 1
ALC05
Alarm comp. backup
ALG01
Clock board error
ALG02
Extended memory error
ALG11
High thermostat alarms Function: 1-5
ALG15
Low thermostat alarms Function: 1-5
ALG19
High modulating alarms Function : 6-7
ALG23
Low modulating alarms Function : 6-7
ALG27
Generic normal alarms Function : 8-9
ALG28
Generic serious alarms Function : 8-9
ALP01
Power + nβ disconnected
ALP03
Compressor start failure (tempt.: / max:)
ALP05
High discharge gas temperature
ALP06
Low pressure differential (insufficient lubrication)
ALT01
Compressors working hours
ALT15
Low superheat alarm
Warning setpoint HPV gascooler press. too different from current
ALT17
setpoint
ALT18
HPV alarm high receiver pressure
ALW01
Warning high pressure prevent
ALW05
Warning Fans inverter
ALW10
Warning Low superheat
ALW15
Warning an error occured during auto-configur.
ALW16
Warning Invalid activation of oil level inputs, check the connections
ALW24
Power + n° Device Offline
ALW25
Power+ n°
ALW26
Compressor start failure (tempt. : / max.: )
Reset
Delay
Automatic
Not present
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Automatic
60 s
Semiautomatic
Config.
Man./Autom
Config.
Automatic
Config.
Automatic
Config.
Automatic
Config.
Automatic
Config.
Automatic
Config.
Man./Autom.
Config.
Man./Autom.
Config.
Man./Autom.
Config.
Automatic
-
Automatic
-
Man./Autom.
Config.
Man./Autom.
Config.
Man./Autom.
Config.
Man./Autom.
Config.
Man./Autom.
Config.
Man./Autom.
Config.
Automatic
Not present
Semiautomatic
Not present
Not present
Automatic
Automatic
Config.
Manual
Not present
Settable
Config.
Automatic
Config.
Automatic
Not present
Automatic
Config.
Not present
Automatic
Not present
Automatic
Not present
Automatic
Automatic
-
Semiautomatic
2 s
Not present
Semiautomatic
Not present
Semiautomatic
Action
Shutdown unit
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Related functions disabled
Shutdown compressor
Shutdown compressor
Fan forcing at 0%
Fan forcing at 100% (5 min.)
and shutdown compressor
-
-
-
Shutdown compressor
Shutdown compressor
Shutdown compressor
Related functions disabled
Related functions disabled
-
-
-
-
-
-
Related functions disabled
5 tries, Shutdown compressor
Shutdown compressor
Shutdown compressor
-
Shutdown compressor
Related functions disabled
Related functions disabled
Related functions disabled
-
-
-
-
Shutdown compressor
Shutdown compressor
-