Recirculation air for heat gain and for avoidance of condensation water
deactivated
Wireless supply air units WFL:
Ventilation if humidity > 80% RH
Ventilation if indoor temperature > 28°C
Winter set-up if outdoor temperature < 1°C
Summer set-up deactivated
Daikin air-conditioning units:
Cooling if indoor temperature > 28°C (cooling in automatic mode)
Heating if indoor temperature < 1°C (heating in automatic mode)
No ventilation if non-operated
Prevent ventilation after air-conditioning: 120 min
Night reduction deactivated
General:
Burglary protection is deactivated
Automatic reset takes place at 3:00 a.m.
Lag period until shadings are extended if sun is shining: 1 min,
retracted: 12 min
Position longitude 8° 49', latitude 48°41'

Units for sun and wind

The intensity of the sun is displayed in lux or kilolux (abbreviated: Kl). The value
1 kilolux is already reached with an overcast sky, at 20 kilolux the sun is just
coming out, and 100 kilolux will be reached in case of cloudless sky at noon.
According to experience, the extension of shadings is recommended with 40
kilolux and more.
The wind speeds are displayed in meter per second, which is abbreviated with
m/s on the display. The ideal wind values for shading and windows depend on
the site of the conservatory and the position of the weather station. Watch the
reaction of the awning or blind or the window with wind and adjust the wind
value adequatly. The following table serves to facilitate identification of the
optimum values for your conservatory: