Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Diagram; Installation Of The Indoor Unit - Daikin FWG05AATNMV1 Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 19
CORK TAPE FULLY INSULATED
INSULATION THROUGH OUT CHILLED WATER PIPING
1. Preliminary Site Survey
Be sure to read this manual before installing the air-conditioner indoor unit.
Voltage supply fluctuation must not exceed + 10% of rated voltage. Electricity supply lines must be independent of
welding transformers which can cause high supply fluctuation.
Ensure that the location is convenient for wiring, piping and drainage.
Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
Do not move the unit from packaging while moving, until it reaches the installation site. Use safe material or protection
plates when unpacking it or lifting it to avoid damage or scratches to the unit.
Obstacle
Ensure a location where:
a)
Drainage can be done easily.
b)
Convenient for wiring and piping.
c)
Which have enough space for installation and service work.
d)
Where no risk of flammable gas leakage.
e)
When free from any obstacles in path of cool air discharge and warm air return and must allow spreading of air
throughout the room (near the center of the room).
f)
Must be provided clearance for indoor unit from the wall and obstacles as shown in figure below.
g)
The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying
noise and vibration.
h)
The installation place (hanging ceiling surface) must be assuring levelness and the height in the ceiling is 350mm or
more.
i)
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
1 IM-CKEW(DC)-1013(1)DAIKIN-EN.i3 3
1 IM-CKEW(DC)-1013(1)DAIKIN-EN.i3 3

INSTALLATION DIAGRAM

2 Pipes System

INSTALLATION OF THE INDOOR UNIT

0.5m or more
Floor
INSULATION THROUGH OUT CHILLED WATER PIPING
0.5m or more
1-3
CORK TAPE FULLY INSULATED
4 Pipes System
0.5m or more
7/1/14 2:39:04 PM