Burner Adjustment Data - elco VECTRON G 06.1200 DUO-PLUS Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Startup

Burner adjustment data

Airflow control
Type
G 06.1200 DUO-PLUS
G 06.1600 DUO-PLUS
G 06.2100 DUO-PLUS
The above adjustment data correspond to the default settings. Pre-delivery adjustment settings appear within a black
rectangle. These settings allow the burner to be run in normal operation, but always carry out a careful check of adjustment
settings, as individual plant conditions may require certain corrections.
The combustion air is regulated at two
points:
· On the pressure side by means of
the opening gap between the
turbulator and burner tube.
· On the suction side by means of the
air flap actuated by servomotor Y10.
36
Dimension
Burner power
kW
700
900
1100
1200
1100
1300
1600
1150
1400
1700
1900
2100
Airflow control in the burner head
has an effect on the air quantity, as well
as on the mixing zone and the air
pressure in the burner tube.
· Adjust dimension Y corresponding to
table of settings.
For this:
· Unscrew the screw 2.
· Slide the RTC plate:
back = more air
forward = less air
m
Do not touch screw 1.
05/2005 - Art. Nr. 13 018 114A
Y
Ignition load
mm
Cam III
25
10
30
10
35
10
40
10
35
10
45
10
50
10
25
10
30
10
35
10
50
10
50
10
Adjusting the gas pressure switch
· Remove transparent cover.
· Settings require the use of an
· Provisionally adjust air-pressure
Adjusting the air-pressure switch
· Remove transparent cover.
· Settings require the use of an
· Provisionally adjust air-pressure
Position of the flap (°)
Full load
Cam I
35
45
50
60
50
80
90
55
65
80
85
90
adjustment disk with a graduated
circular dial and an index.
switch to minimum setting.
adjustment disk with a graduated
circular dial and an index.
switch to minimum setting.