Verfügbare Sprachen

Function
VGD gas valve assembly with SKP controller
Burner G 06.1200 DUO-PLUS
Gas:
pressure(s)
E-Gas: 20, 25
(Schr. R)
LL-Gas: 20, 25
(Schr. D)
Burner G 06.1600/2100 DUO-PLUS
Gas:
pressure(s)
E-Gas: 20, 25
(Schr. R)
LL-Gas: 20, 25
(Schr. D)
Bold print: factory supply
Gas-pressure switch adjustment
· Remove transparent cover.
Adjustment is carried out by turning
the adjustment screw with circular
scale and index x.
· Adjust provisionally to minimum
setting.
VGD
VGD
Rp2
DN65
1,4
1,3
2
2
VGD
VGD
Rp2
DN65
1,3
2
05/2005 - Art. Nr. 13 018 114A
1
Electrical connection for gas
pressure switch (DIN 43650)
2
Electrical connection for magnetic
valves (DIN 43650)
3
Gas pressure switch
4
Input flange
5
Pressure measuring nipple R1/8,
ahead of filter (both sides)
6
Filter (under cover)
7
Type plate
8
Connection for air pressure pipe
pL R1/8
9
Setting screw for V ratio
12
Setting screw for zero value N
13
Connection for furnace pressure
take-off pipe pF, R1/8
14
Connection for gas pressure
take-off pipe pG, R1/8
15
Output flange
16
Pressure release pipes
pBr (pG)= Gas pressure release
pF =
Furnace pressure release
pL =
Air pressure release
SKP controller with VGD valve ensures
a constant ratio between gas flow and
air flow thanks to an adjustable ratio
D = pressure adjusting screw
(air excess)
R = pressure adjusting screw
(Gas/air ratio)
Adjustment
level of "R" ratio
EN
Adjustment level
of D
Gas valve
opening display