Verfügbare Sprachen

Function

TC Control panel

TC Control panel
All control components are visible from
the outside. A transparent detachable
lid clipped on the cover provides access
to the different controls and control
components for settings and burner
operation.
The control panel also includes a
measuring bridge for the flame signal,
as well as a protective fuse.
30
To detach the lid, press slightly to one
side, or on both sides, and remove
simultaneously.
To replace the lid, place the 2 clips in
front of their corresponding orifices
and press.
Optional:
hour meter (connection cable
already in place)
RWF 40 three point stage controller
in the standard position.
05/2005 - Art. Nr. 13 018 114A
Functions
A2
Standard 48x48 or 48x96 mm
positions for the installation of a
power controller (optional)
A4.1 Position with clips for the display
B10 Mesuring bridge [µA DC] for cell
current, placed next to the motor
contactor
F10 Fuse
S1
Main switch
0
OFF
1
ON, green light
H10 lit on the switch
S2
Selection of power regulation
K
Manual mode
Auto Automatic local mode
S3
Operates in connection with
switches
S28J - S2K
+/-
power increase/power
decrease
S5
Remote unit switch:
- fault display, red H6 light lit
- reset push-button
S28 Choice of control venue
J
Local Mode
H
Remote control mode
(optional)
m
Caution:
The main switch on the control panel
only sets off control voltage. Prior to all
action in the section of the burner
switch, turn the burner off, including the
triphase burner motor connection.