Do not allow any chemicals to come in contact
with the condensate pump. Please remove the
pump and water sensor before using any coil
cleaning solutions and other chemicals. Flush the
evaporator coils with water before reinstalling the
condensate pump and water sensor. Ensure the
evaporator coils are free of chemicals before
reinstallation of the REFCO Combi pump.
Installation cable must not experience a tensile
load.
Installation cable must be completely pushed into
the jack. Only use the original installation cable.
Do not install items nearby with significant heat
impact on the pump.
Power supply to the pump must be current
limited to less than 7A.
The indoor unit wired through violet and grey
alarm wires must not pull more than 5A.
The pump must not be exposed to sunlight.
Intended Use
The VAMP-X condensate pump is intended for use as condensate
removal unit and must be installed fully within enclosures of electric
heat pumps, air-conditioners indoor units and dehumidifiers. This
includes ceiling cassettes, underfloor convectors and wall-mounted
convectors.
It is for indoor use only and it is not submersible.
Instruction Manual
5