Fronius Primo 4.5-1 Serviceanleitung Seite 105

Netzgekoppelter wechselrichter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code
Description
998
Fronius Solar.net loop is
open 24 hours
999
No power fed into mains for
a 24-hour period
1000* -
Service messages
1001*
1201* -
Service messages
1210*
* ... Code only appears during event logging and on the error counter
Behaviour
Fronius Solar.net is not closed
and X-LED on Datalogger or
Datamanager lights up red
1. No answer from inverter for
24 hours -> Notification to Dat-
alogger or Datamanager
2. No answer from Fronius
Sensor Card for 2 hours -> No-
tification to Datalogger or Data-
manager
Harmless if energy is being fed
into the grid correctly - pro-
vides information on the status
of the internal processor
Harmless if energy is being fed
into the grid correctly - pro-
vides information on the status
of the internal processor
Remedy
1. Check Fronius Solar.net
loop
2. Check network cable
3. Check Fronius Com Card
1. Check LED status of Data-
manager or Datalogger
2. Check Fronius Solar.net
loop and archive values
105