12
Date of first day of
holiday
13
Date of last day of
holiday
14
Heating curve, flow
setpoint at 15 °C
outside temperature
15
Heating curve, flow
setpoint at –5 °C
outside temperature
26
Setpoint d.h.w.
temperature
NORMAL
27
D.h.w. temperature
28
Setpoint d.h.w. tem-
perature REDUCED
31
Weekday (for switch-
ing program 2)
32
Start of first ON
period
33
End of first ON
period
34
Start of second ON
period
35
End of second ON
period
36
Start of third ON
period
37
End of third ON
period
38
Time of day
Building Technologies
--.--
(01.01 ... 31.12)
.........................
--.--
(01.01 ... 31.12)
.........................
30 °C
(20...70)
...................
60 °C
(20...120)
...................
55 °C
(20...100)
...................
Display function
40 °C
(8...80)
...................
1-7
(1...7)
.........................
05:00
(00:00...24:00)
.........................
22:00
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
--:--
(00:00...24:00)
.........................
00:00...23:59
74 319 0619 0 a
Day.Month
Day.Month
These operating lines are only
°C
active if digital adjustment of the
heating curve has been se-
lected (refer to entry made on
°C
operating line 73)
°C
With plant types x–0 and x–4,
these operating do not appear
°C
1 = Monday
2 = Tuesday, etc.
1-7 = entire week
Switching program 2
--:-- = period inactive
Hours:Minutes