Electrical installation
Networks
Modbus RTU
Modbus RTU
The network must be terminated with a 120 Ω resistor at the physically first and last node.
Set the "R" switch to ON at these nodes.
Typical topologies
A1
A2
120
X216
X216
TA
TB
COM
Terminal description
Connection
Connection type
Max. cable cross-section
mm²
Max. cable cross-section
AWG
Stripping length
mm
Stripping length
inch
Tightening torque
Nm
Tightening torque
lb-in
Required tool
Basic network settings
Use the DIP switch to set the node address and baud rate and to activate the integrated bus terminating
resistor.
Bus termination
Baud rate
R
c
OFF
n.c.
OFF
Inactive
Automatic detection
ON
ON
Active
Value from parameter
Bold print = default setting
86
Line
A3
120
X216
TA
TB
COM
TA
pluggable double spring terminal
R
c
b
a 128
64 32 16 8
Mode
Address
Parity
b
a
OFF
Automatic detection
ON
Value from parameter
An
120
120
X216
TB
COM
TA
Modbus RTU
X216
2.5
12
10
0.39
-
-
0.4 x 2.5
4
2
1
O
N
Modbus node address
128
64
32
16
8
OFF OFF OFF OFF OFF OFF OFF OFF
Value from parameter
Node address - example:
OFF
OFF
OFF
ON
OFF
ON
Node address = 16 + 4 + 2 + 1 = 23
Node address > 247: value from parameter
TB
COM
4
2
1
ON