3-phase mains connection 400 V "light duty"
Connection diagrams
See
"Connection
diagrams".
^ 76
Terminal data
See
"Terminal
data".
^ 77
Fusing data
Fusing data
Inverter
Cable installation in compli-
ance with
Installation method
with mains choke
Fuse
Characteristics
Max. rated current
A
Earth-leakage circuit breaker
3-phase mains connection
Fusing data
Inverter
Cable installation in compli-
ance with
Installation method
with mains choke
Fuse
Characteristics
Max. rated current
A
Type of fusing
SCCR: requirement
SCCR: max. short circuit
kA
current
SCCR: voltage
Earth-leakage circuit breaker
3-phase mains connection
3-phase mains connection 400 V "light duty"
I55AE355F
I55AE375F
EN 60204-1
F
gR
160
160
≥ 300 mA, type B
I55AE355F
I55AE375F
US National Electrical Code NFPA 70 / Canadian Electrical Code C22.1
acc. to UL 248 / Class J (recommended: HSJ by Mersen)
200
200
Standard
Standard short-circuit strength
10
10
480/277 Volts Maximum
≥ 300 mA, type B
Electrical installation
Mains connection
I55AE390F
I55AE411F
300
300
I55AE390F
I55AE411F
300
300
10
10