78
7. TROUBLESHOOTING
Typical alarms and faults:
To check the UPS status and Event log:
The following table describes typical conditions:
Press any button on the front panel display to activate the
menu options.
Press the button to select Event log.
Scroll through the listed events and faults.
Conditions
Possible cause
Battery mode
A utility failure has
occurred, and the
UPS is in Battery
mode.
LED is On. 1
beep every 4
seconds.
Battery low
The UPS is in Battery
mode and the battery
is running low.
LED is On.
1 beep every
second.
No battery
The batteries are
disconnected.
LED is On.
Beep
continuous.
Battery fault
The battery test is
failed due to bad or
disconnected
batteries, or the
LED is On.
battery minimum
Beep
voltage is reached in
continuous.
OBM cycling mode.
Action
The UPS is powering the
equipment with battery power.
Prepare your equipment for
shutdown.
This warning is approximate, and
the actual time to shutdown may
vary significantly.
1. Verify that all batteries and
detective cable (RJ45) are properly
connected.
2. Check the LCD menu: Settings –
External battery. If select
the "Manual EBP" and Value is 0,
please set the right
value.
Verify that all batteries are properly
connected. Start a new battery test:
if the condition persists, contact
your service representative.