AEG Protect C 1000 LCD+ Benutzerhandbuch Seite 80

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

80
Conditions
Possible cause
connector is missing.
Emergency
RPO is active
power off
Fan fault
Fan abnormal
Site fault
Phase and neutral
conductor at input of
UPS system are
reversed
Over
Over temperature is
temperature
too high, UPS goes
fault
to bypass or stopped.
Output short
Output short circuit
circuit
occurred.
Action
1.Check the RPO connector status
2.Reset the RPO fault through
LCD. Main menu – Control - Reset
fault state.
Check if the fan is running normally
Site Fault detection disabled by
default. It can still be enabled /
disabled from the LCD settings
menu.
Reconnect all input wires.
Check the ventilation of the UPS
and check the ambient
temperature.
Check the output of UPS and
loads, make sure the short circuit is
removed before turning on again.