Herunterladen Diese Seite drucken

Endress+Hauser PROline 93 II2G Serie Bedienungsanleitung Seite 63

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PROline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
Bus cable type 3076 from Belden (shielded bus cable):
• Nominal values:
24 Ω /km (loop resistance)
R'
=
C'
=
82 nF/km (capacitance per unit length between the two wires)
623 µ H/km (inductance per unit length of the two wires)
L'
=
C'
=
147 nF/km (capacitance per unit length wire against shielding)
LS
Bus termination:
• Nominal values:
U
=
30 V
i
P
=
1.2 W
i
C
=
negligible
i
The effective capacitance of the bus line is derived first from the capacitance per unit
length C', which is effectively the capacitance between the two wires. In the case of the
shielded wires the order of capacitance "wire against shielding" and "shielding against
wire" must be observed. The total capacitance of the bus line is thus calculated as fol-
lows:
C'
= (C' + 0.5 x C'
eff/cable
The total length of the bus line L
length of all spurs. Using the system structure illustrated in Fig. 9 the following data rel-
evant to safety emerges for the bus line:
+ Σ L
L
=
L
SEG
main
=
580 m + 35 m
=
615 m
C'
=
(C' + 0.5 x C'
eff./cable
=
(82 nF/km + 0.5 x 147 nF/km) x 0.615 km
=
95.6 nF
L'
=
L' x L
eff./cable
SEG
623 µ H/km x 0.615 km
=
383.1 µ H
=
) x L
LS
SEG
is made up of the length of the main cable and the
SEG
spurs
) x L
LS
SEG

25

Werbung

loading

Diese Anleitung auch für:

Proline 93 ii21g serie