Herunterladen Diese Seite drucken

Endress+Hauser PROline 93 II2G Serie Bedienungsanleitung Seite 62

Werbung

Verfügbare Sprachen

Verfügbare Sprachen


24
Checking the conditions:
Consideration
≥ I
I
seff
SEG
71.2 mA ≥ 54 mA
≥ 9 V
U
FG eff.
11.2 V ≥ 9 V
Final consideration:
From a purely functional point of view the bus segment shown in the example can be
operated based on the positive results. Further optimization of the network with a view
to connecting a greater number of field devices or realizing a longer line length can be
achieved by selecting the right fieldbus power supply and cable type.
Technical safety considerations
using variant Prosonic Flow 93***-***********G
Step 1 – compilation of technical values relevant to safety:
Bus power supply MTL 5053 (associated electrical apparatus)
• Nominal values:
U
=
22 V
o
I
=
216 mA
o
P
=
1.2 W
o
Capacitance C
o
Inductance L
o
L/R
ratio
Tab. 5:
External connection values of bus power supply MTL 5053 depending on temperature class
Prosonic Flow 93 (explosion protected electrical apparatus with intrinsically safe FF out-
put):
• Nominal values:
U
=
30 V
i
I
=
500 mA
i
P
=
5.5 W
i
10 µ H
L
=
i
C
=
5 nF
i
Cerabar S (explosion protected electrical apparatus with intrinsically safe FF output):
• Nominal values Entity:
U
=
24 V
i
I
=
250 mA
i
P
=
1.2 W
i
10 µ H
L
=
i
C
=
5 nF
i
PROline Prosonic Flow 93 FOUNDATION Fieldbus
Condition met?
Yes

Yes

Explosion group
IIC
0.165 µ F
0.32 mH
31 µ H/ Ω
IIB
1.14 µ F
4.20 µ F
3.00 mH
7.00 mH
126 µ H/ Ω
242 µ H/ Ω
Endress+Hauser
IIA

Werbung

loading

Diese Anleitung auch für:

Proline 93 ii21g serie