GB
• IAQ — indoor air quality sensor (CO
temperature)
• CO2 — CO
duct sensor
2
• 1 — Outdoor air
• 2 — Supply air
• 3 — Extract air
• 4 — Exhaust air
Component/product — Article number:
• Systemair-1 CO2 duct sensor — 14906
• Systemair-E CO2 sensor — 14904
• Room sensor 0-50C (temperature) — 211525
• Systemair-E CO2 RH Temperature — 211522
Installation and connection
1. Install IAQ sensor in the duct or the room depending on
the transmitter type.
2. Connect CO
sensor to any free universal analog input
2
(UI) on the connection board.
3. If IAQ sensor contains relative humidity transmitter:
Connect it to any free universal analog input (UI) on the
connection board.
4. If IAQ sensor contains room temperature transmitter:
Connect it to any free analog input (AI) on the connec-
tion board (only AI6 and AI7 are available on the con-
nection board).
Configuration
1. Go to Service menu.
2. Enter password (default 1111).
3. Configure of CO
and/or relative humidity sensor: Go to Input menu. Select UNIVERSAL tab. Select the universal in-
2
put to which the sensor is connected. Example if it is connected to UI4 on the connection board, then select UNIVER-
SAL INPUT 4. Select signal type as Analog input and select sensor type from the input type list: RH sensor (RH)
and/or CO₂ Sensor (CO₂).
4. Configure room temperature sensor: Go to Input menu. Select ANALOG tab. Select the analog input to which the
sensor is connected. Example if it is connected to AI6 on the connection board, then select ANALOG INPUT 6. Select
input type as Room Air Temperature Sensor (RAT).
11.3 Temperature control
11.3.1
Electrical duct pre-heater
Electrical pre-heater can be installed in the outdoor air duct to pre-heat out-
door air before it reaches the unit and prevent icing in the heat exchanger.
212024 | A003, rev 29
, RH and
2
Accessories |
Fig. 10 IAQ connections
55