5.3
Fuses
Only R. STAHL is permitted to install, modify or retrofit fuses.
When fitting fuses, the following temperature classes of the associated ambient temperature
values apply:
Fuse current value
≤ 2 A
> 2 to ≤ 5 A
> 5 to < 6.3 A
When fitting fuses, the temperature classes of the associated ambient temperature values
apply for the following maximum permissible surface temperatures in dust hazardous areas:
Fuse current value
≤ 2 A
> 2 to ≤ 4 A
> 4 to ≤ 5 A
> 5 to < 6.3 A
133275 / 8118605300
2023-08-10·BA00·III·en·09
Product Selection, Project Engineering and Modification
Temperature class
T6
T5
T4
Ambient temperature
(T
)
a
≤ 40 °C
≤ 55 °C
≤ 40 °C
≤ 55 °C
Max. permissible
surface temperature
T80 °C
T95 °C
T95 °C
T130 °C