Operation and configuration of packaged units
4.7.2 Values table for packaged units
Identifier of the type of file:
Temporary identification and module:
Adjustment of the indoor unit (CSNET Manager):
Central:
<Central=1/Local=0>
Set Mode:
<Adjustment of the operation mode: FAN=0, COOL=1, DRY.=2, HEAT=3, AUTO=4>
Set Fan:
<Adjust the fan speed (not Utopia): LOW=2, MEDIUM=3, HIGH=4>
Set Swing L:
(Swing Louver)<Adjust swing louver: Position = 0-6, AUTO=7>
ON/OFF:
<On=1/off=0 adjustment>
Tset:
<Setting temperature in ºC>
Communication:
Alarm:
<Error code>
Comp.Stopped:
<Cause of compressor stop>
Valid:
<Valid data>
Bit 0=1 (value 1): The data read from the indoor unit are valid except for the opening of the expansion valve and
operating state
Bit 0=1 (value 2): (not Utopia): The data of the expansion valve opening of the indoor unit are valid
Bit 0=1 (value 4): (not Utopia): The data on the operating condition of the indoor unit are valid
Bit 3=1 (value 8): (not Utopia): The data on the outdoor unit are valid, the total should be 15 for SET FREE and 1 for
UTOPIA
Readings for the indoor unit:
Mode:
<IU: Reading of the operating mode (not Utopia): FAN=0, COOL=1, DRY=2, HEAT=3>
Fan:
<IU: Reading of the fan speed (not Utopia): STOP=0, SLOW=1, LOW=2, MEDIUM=3, HIGH=4>
Status:
<IU: Reading of the operating condition: STOP=0, THERMO ON=1. THERMO OFF=2, ALARM=3>
Swing L:
<IU: Reading of the swing louver: POSITION=0-6, AUTO=7, NOT AVAILABLE=8>
IU Hz:
<IU: Reading of the required frequency>
Ti:
<IU: Reading of air inlet temperature in ºC>
To:
<IU: Reading of air outlet temperature in ºC>
IncT:
<IU: Reading of the absolute value of the inlet-outlet temperature in ºC>
Tg:
<IU: Reading of gas piping temperature in ºC>
Tl:
<IU: Reading of liquid piping temperature in ºC>
TRem:
<IU: Reading of the thermistor temperature in ºC> *1
Tset Read:
<IU: Reading of setting temperature in ºC>
iE:
<IU: Reading of % opening of the expansion valve > (% x 1000 in version 2)
63
PMML0303A rev.2 - 02/2015
<Type=Version; 3 or 2>
<Year> <Month> <Day> <Hour> <Minutes>
<CS Port> <OU Number> <IU Number>