Operation and configuration of packaged units
4.6.4 Modbus server
CSNET Manager can work as a Modbus server. This configuration is done on the "Modbus" panel.
On this panel it can be configured if the function is enabled or not, and the listening port of the CSNET Manager.
The table displays the different units, where it can be modified the Modbus ID. This Modbus ID modifies the register address for read
the data of this unit. It will automatically displayed on the column "register" the number of the register where the unit begin.
The extra options let the user save the table data to a file or copy to the clipboard. Auto set Id option put correlative ids to the
different units.
Address
Name
(Note 1)
0
EXIST
1
SYSTEM_ADDRESS
2
UNIT_ADDRESS
3
SET_ONOFF
4
SET_MODE
5
SET_FAN
6
SET_TSET
7
SET_LOUVER
45
PMML0303A rev.2 - 02/2015
Description
0: Not exist
1: Exist
H-LINK 1: 0~15
H-LINK 2: 0~63
ON/OFF setting order:
0: Stop
1: Run
Mode setting order:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan setting order:
0: Low
1: Medium
2: High
Setting temperature
17ºC ~ 30ºC
Louver setting
0 ~ 8 (8 is Auto)
Read/Write
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write