Operation and configuration of packaged units

Description of parameters
To use this option, you have to set the parameters shown in the Auto Cool/Heat operation panel. After that, if unit is working in Auto
Cool/Heat mode, you can see the status of this operation on the status zone of the panel.
The Auto Cool/Heat panel shown corresponds to the cooling circuit of the indoor unit selected in the table of indoor units, as shown
in the example.
You should adjust the following parameters:
Unit configuration
Master unit: Field for selecting the method CSNET will use to calculate the temperature difference.
-
-
 
(Marked): CSNET will only use this unit to calculate the temperature difference and decide the change, not taking
into account the other units connected to the same 2-tube cooling circuit.
(Not marked): CSNET will use the average temperature difference of all the indoor units connected to the same
-
 
2-tube cooling circuit.
!
C A U T I O N
When this method is used (marked), the following outdoor unit option cannot be used: "control of indoor unit fan speed" (during operation with the
thermostat deactivated in heat mode, the indoor fan stops for 6 minutes and operates for 2 minutes). If it is used, the decision of when to change will
not always be correct (if it is measured during the deactivation cycle of 6 minutes).
-
Select input data: field for selecting what inlet temperature CSNET should use to calculate the temperature difference if an
optional remote temperature sensor is connected in THM4 of the PCB of the indoor unit or if there is RCS remote sensor.
When there are selected a combination of different sensor it will calculate the average between them. When nothing is
selected, it is forced to use the Tin value.
-
Minutes between change mode: The time which must elapse between the last change of operation mode to the next
change.
Š Pre set adjustment: 20 min.
Š 10 min steps.
Š 20 min... 60 min margin.