Page 21 of 30 of European Technical Assessment ETA-22/0275, issued on 2022-11-07
Table C2.1:
Characteristic buckling load resistance P
thermal separation module under pressure load with or without shear load
displacement 
Insulation
thickness (incl.
Type
insulation
plaster and t
[mm]
HIK-T 12
60 - 120
HIK-T 12
121 - 160
HIK-T 12
161 - 220
HIK-T 16
60 - 220
HIK-T 16
221 - 300
* 
for buckling in accordance with EOTA TR 077
Mca
**calculated values in accordance with Euler cases were decisive for the determination of
performance
HIK-T 12, HIK-T 16
Performances
Characteristic buckling load under pressure load
V
HIK-T 12, HIK-T 16
Max. shear
load
displacement
)
tol
h
D
V
[mm]
5
5
5
5
5
for the system of threaded rod and
Rk,ca
Euler case 1
Lr for free rotatable
Free rotatable
(Euler case 1)
Char.
buckling load
resistance
Lr
P
Rk,ca
[mm]
[kN]
≥ 15,8**
136,4
≥ 9,4**
176,4
≥ 5,2**
236,4
≥ 17,9**
238,4
≥ 10,0**
318,4
Euler case 2
Lr for not free rotatable
Not free
rotatable
(Euler case 2)
Char.
Safety
buckling load
factor
resistance
P
Rk,ca
[kN]
≥ 25,2
≥ 25,2
≥ 21,0**
≥ 22,7
≥ 22,7
Annex C2
*
Mca
[-]
1,3
1,3
1,3
1,3
1,3