14.2 INSTALLING THE CONTROL PANEL ON THE WALL

For the boiler to work with the Control Panel mounted on the wall, purchase accessory B supplied with the base B1 and position it
on the boiler as shown in the figure. Also see the mounting and operation instructions supplied with the kit B. Proceed as follows:
• Switch off the boiler.
• Pass the three wires from the boiler terminal block M2 through the hole in the base B1 to apply to the wall.
• Connect wires 1-2-3 of the boiler terminal block M2 to terminals (1)-(2)-(3) of the base terminal block B1 respectively.
• Fix the base B1 to the wall using the expansion grips and screws supplied with the accessory.
• Apply the Control Panel A to the base fixed to the wall, taking care not to apply excessive force.
• Place accessory B on the front boiler panel.
• Power the boiler making sure that the Control Panel lights up.
The wire (1) from the boiler terminal block M2 powers the display backlighting (12 V). This wire does not have to be connected
for the wall-mounted Control Panel to work.
KEY TO WALL-MOUNTED CONTROL PANEL CONNECTIONS
A
Control Panel
(1)
Display backlighting +12V
For the wall-mounted Control Panel to work it must be configured (ambient probe and modulating flow temperature enabled).

14.2.1 PARAMETERS SETTING

ALL MODIFIED PARAMETERS SHOULD BE NOTED DOWN IN THE TABLE AT THE END OF THIS MANUAL.
KEY TO FIGURE MENU
1
Enduser
2
Commissioning
The following procedure is used to access the four boiler
programming menus:
• from the main menu
A and C (hold down for approx. 6 seconds)
B
menu 1-2-3-4 (see figure to side and key).
C to go back one menu at a time to the main menu.
When the Control Panel is wall-mounted enable the room
sensor and flow temperature modulation as follows:
A) ROOM SENSOR
• Access menu 2.
B
Operator unit
B
programme row 40 (Used as)
B (anti-clockwise)
C to return to the previous menu then
B
programme row 5977 (Function input H5) then
B
None
B to confirm.
B
Led interface accessory
(2)
Earth connection
3
Engineer
4
OEM
C.
B to confirm.
B.
Room unit 1
B to confirm (the room sensor is now active).
B
Configuration
B.
B to confirm.
45
B1
Base for wall-mounted Control Panel
(3)
Power input/Signal +12V
7219836.01 (1-04/15)