Menu Structure; Thyro-Tool Ax - Advanced Energy THYRO-AX Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

62

7.8 MENU STRUCTURE

MENU
SUBMENU
DEFAULT VALUE
ActVal
Event
Settings
Operating
1A: TAKT, 2A: TAKT,
3A: VAR
Regulator
U x U
Limit
Type values of the
device
Takt
CyclTime
50 per
(for operating mode
Alpha1st
1A: 60° el, 2A: 90° el,
TAKT)
3A: 90° el
SST
6 per
Switch
Alpha1st
1A: 60° el, 2A: 90° el,
3A: 90° el
(for operating mode
SST
6 per
SWITCH)
Monitoring
R_Max = (type voltage
* 2)/type current
AS 1
0-20mA
AS 2
0-20mA
AO 1
Range
0-20mA
Source
Average
Value
OFF
ValuePh
AO 1: U, AO 2: I, AO
3: OFF
ScaleMax
AO 2
(like AO 1)
AO 3
(like AO 1)
ReadSet
Code
Save
Load
Load EEPROM
Load Factory Set.
TeachIn
EasyStart
Eth.Set.
DHCP/Static
DHCP
IP Adr
192.168.0.100
Submask
255.255.255.0
Gateway
192.168.0.254
1. DNS
194.25.2.129
2. DNS
130.146.25.194
USB Menu
TAB. 9 MENU STRUCTURE THYRO-AX
REMARKS
Main menu of the current value overview. Also appears
automatically after a period of 30 sec. of not changing
List of all current active messages (events).
OK has the function of acknowledging the relevant message.
Operating mode, operating of thyristors
Current, voltage or power based control.
Maximum value for current, voltage and power.
Cycle period
Phase angle of the 1st half wave
Soft-start time
Phase angle of the 1st half wave
Soft-start time
R_Max for load monitoring
Signal for analog setpoint 1
Signal for analog setpoint 2
Dimensions for analog output 1
Source for measurment (crucial if Value or ValuePh will be
displayed).
Output of general values (source must be set to general).
Output of phase related values (source must be set to L1, L2,
L3, Min, Max or average).
Full scale value
Overview of all device parameters.
Authorization code for parameter changes and digital
setpoint entry at display.
Save the current parameters in EEPROM. This is shown
automatically after a modification, when the menu is
acknowledged.
Load customer parameters from EEPROM.
Load default settings.
Start the load measuring for automatic load failure detection.
Start the quick configuration of the device by basic
parameters.
Method of assigning IP address.
Read the assigned IP address or write the static one.
Subnet mask of network.
Gateway of network.
IP of domain name server 1.
IP of domain name server 2.
Read and write the parameters via USB flash drive.

7.9 THYRO-TOOL AX

The software Thyro-Tool AX (hereafter referred to as Tool) is suitable
for parameterization and visualization of connected devices of series
Thyro-AX. Parameter and line charts can be saved. During installation
a server (Windows service: ThyroWindowsService) and client will be
installed, which will be started parallel in the simplest case. There is an
option to access device, which are connected to a computer, by using
remote maintenance on another computer.
FIG. 9 CONNECTION TO LOCAL INSTALLED SERVER
The left side of the window offers an own explorer for open files and
directly connected devices. On the right side, tabs are shown for each
subsection which has been selected by double clicking on it. There are
3 different options to switch between the open windows:
- Double click on explorer (like opening for the first time)
- Select tab
- Drop-down menu (Overview with icons)
FIG. 10 SEVERAL OPEN TABS
The field with status messages can be transferred as an external win-
dow back and forth for an improved overview. Therefore stretch out the
63