12 Device information
1
Type and order code
2
Design
Heat source
2.1
Model
2.2
Controller
2.3
Thermal energy meter
2.4
Installation location
2.5
Performance levels
3
Operating limits
3.1
Heating water flow
3.2
Cold waterRC (heat source)
4
Flow / sound
4.1
Heating water flow / free compression (max).
Nominal flow in accordance with EN 14511
Minimum heating water flow
4.2
Cold water flow rate / internal pressure differential
Nominal flow in accordance with EN 14511
Minimum cold water flow rate
4.3
Sound power level according to EN 12102
4.4
Sound pressure level at a distance of 1m
5
Dimensions, weight and filling quantity
2
5.1
Device dimensions
5.2
Weight of the transportable unit(s) incl. packaging
5.3
Device connections for heating
5.4
Device connections for heat source
5.5
Refrigerant / total filling weight
5.6
GWP value / CO
equivalent
2
5.7
Refrigeration circuit hermetically sealed
5.8
Lubricant / total filling quantity
5.9
Volume of heating water in device
5.10 Volume of heat transfer medium in device
6
Electrical connection
6.1
Supply voltage / fuse protection / RCD-Type
6.2
Control voltage / fuse protection / RCD-Type
6.3
Degree of protection according to EN 60 529
6.4
Starting current with soft starter
6.5
Nominal power consumption W10/W35
/ max. power consumption
Nominal current W10/ W35 / cos 
6.6
6.7
Power consumption of compressor protection
(per compressor)
6.8
Power consumption of pumps
EN-12
°C
°C
at W10...7 / W35...30
m³/h / Pa
at W10...7 / W45...40
m³/h / Pa
at W10...7 / W55...47
m³/h / Pa
m³/h / Pa
at W10...7 / W35...30
m³/h / Pa
at W10...7 / W45...40
m³/h / Pa
at W10...7 / W55...47
m³/h / Pa
m³/h / Pa
dB(A)
1
dB(A)
H x W x L mm
kg
inches
Inches
type/kg
--- / t
type/litres(max.
Litres
Litres
A
3
kW
A / ---
W
kW
452237.66.11 · FD 9908
WI 65TU
Water
Universal
WPM Econ5Plus integrated
Integrated
Indoors
2
20 to 62 ± 2
+7 to +25
12.1 / 48000
11.1 / 54000
6.5 / 77000
6.5 / 77000
16.0 / 47000
14.1 / 37000
12.5 / 29000
12.5 / 29000
61
45
1665 x 1000 x 805
465
Rp 1½"
Rp 2½"
R410A / 16.8
2088 / 35
yes
Polyolester (POE)/7.3
13
13
3~/PE 400 V (50 Hz) / C 40A / A
1~/N/PE 230 V (50 Hz) / C 13A / A 1~/N/PE 230 V (50 Hz) / C 13A / A
IP 21
56
11.1 / 18.4
23.0 / 0.8
90 / thermostatically controlled
up to 0.26
WI 65TU - WI 95TU
WI 95TU
Water
Universal
WPM Econ5Plus integrated
Integrated
Indoors
2
20 to 62 ± 2
+7 to +25
17.0 / 34000
16.2 / 41000
9.7 / 86000
9.7 / 86000
23.2 / 42000
20.6 / 33000
18.9 / 28000
18.9 / 22000
62
46
1900 x 1350x 805
565
Rp 2"
Rp ½"
R410A / 23.0
2088 / 48
yes
Polyolester (POE)/7.3
18
18
3~/PE 400 V (50 Hz) / C 50A / A
IP 21
62
16.8 / 26.8
34.8 / 0.8
90 / thermostatically controlled
up to 0.43
www.gdts.one