Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy Quattro 12/3000/120 Anleitung Seite 22

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 83
DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel or 3-phase operation
Stand-alone operation (see figure 1)
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC-in-1
Set as desired
DS-7 AC-in-1
Set as desired
DS-6 AC-in-1
Set as desired
DS-5 AC-in-2
Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
DS-1 Stand-alone operation
Examples of DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set
to 'off' and do not reflect the actual settings in the microprocessor).
Important: When a panel is connected, the AC-in-2 current limit is determined by the panel and not by the value stored in the
Quattro.
Four examples of stand-alone settings:
DS-8 AC-in-1
on
DS-7 AC-in-1
on
DS-6 AC-in-1
on
DS-5 AC-in-2
on
DS-4 Charging current
on
DS-3 Charging current
DS-2 Stand-alone mode
DS-1 Stand-alone mode
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in-1: 50A
5 AC-in-2: 30A
4, 3 Charge current: 75%
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of
the DIP switches, see appendix A, position K). The overload and low-battery LED's will flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
18
off
off
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
off
DS-2
off
off
DS-1
off
off
Step1, stand-alone
Example 2:
8, 7, 6 AC-in-1: 50A
5 AC-in-2: 16A
4, 3 Charge: 100%
2, 1 Stand-alone
DS-8
off
DS-8
DS-7
on
DS-7
DS-6
on
DS-6
DS-5
off
DS-5
DS-4
on
DS-4
DS-3
on
DS-3
DS-2
off
DS-2
DS-1
off
DS-1
Step1, stand-alone
Step1, stand-alone
Example 3:
Example 4:
8, 7, 6 AC-in-1: 16A
8, 7, 6 AC-in-1: 30A
5 AC-in-2: 16A
5 AC-in-2: 30A
4, 3 Charge: 100%
4, 3 Charge: 50%
2, 1 Stand-alone
2, 1 Stand-alone
on
on
off
on
off
on
off
off

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Quattro 12/3000/70Quattro 12/3000/35

Inhaltsverzeichnis