ONE STAGE LIGHT OIL BURNERS
N° 0002934100

INSTALLING ON BOYLER

Rev. 10/02/2004
1) Lock the flange B on the tube of the burner via the supplied screw A and nut C (n° 2 x BTL 20).
2) Position the insulating seal E on the tube, interposing the cord F between flange and seal.
3) Finally, fix the burner to the boiler via the 4 stud bolts and relative nuts (supplied).
N.B. Make sure the tube penetrates into the combustion chamber as per the boiler manufacturer's
instructions.

APPLIANCE SPECIFICATIONS

Extraneous light / advanced ignition
During the pre-ventilation and/or pre-starting phase there
shall be no flame signal. Should the signal be present, for
example for advanced ignition due to bad tightness of the
electrovalve, external lighting, short-circuit in the photo-
resistance or in the connecting cable, a breakdown in the
flame signal amplifier, and so on., when the pre-ventilation
and safety time has elapsed, the control-box brings the
burner to the emergency stop and cuts off fuel inflow even
during the safety time.
No flame
If there is no flame at the end of the safety time, the control-
box stops the burner immediately.
No flame during operation
If there is no flame during operation, the control-box cuts
off fuel and automatically repeats a new starting program:
once the "t4" time has elapsed, the starting program is
over.
Every safety stop of less than 1 second switches off voltage
to terminals 3 - 8 - 11: and to terminal 10, it is possible to
provide a remote signal of emergency stop. Resetting of
the control-box is possible after approx. 50 seconds of
emergency stop.
17