Herunterladen Inhalt Inhalt Diese Seite drucken

Applicable Controls - Toshiba MMU-UP0091H-E Installationsanleitung

Vorschau ausblenden Andere Handbücher für MMU-UP0091H-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25
8

Applicable controls

REQUIREMENT
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatically
address setup, it takes up to 10 minutes (usually
about 3 minute) for the outdoor unit to start operating
after the power has been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a wireless
remote controller and simple remote controller by itself
so install a wired remote controller separately as well.
227-EN
 Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU11-
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
CAUTION
Set only the Code No. shown in the following table: Do
NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
3,6
2,4,5
4,5
1
7
1
Push and hold menu button and [
] setting
button simultaneously for 10 seconds or
more.
• After a while, the display flashes as shown in the
figure. "ALL" is displayed as indoor unit numbers
during initial communication immediately after the
power has been turned on.
Indoor unit No.
2
Each time [
] [
] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs and the
louvers start swinging. The indoor unit can be
confirmed for which to change settings.
3
Push OFF timer button to confirm the
selected indoor unit.
Set data
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
[
] setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
with [
] [
] setting button.
6
Push OFF timer button to complete the set
up.
• To change other settings of the selected indoor
4
unit, repeat from Procedure
.
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode)
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit,
1
repeat from Procedure
.
– 114 –
 Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
1
2
3
4
5
6
(
[5d]
• Specify
for the Code No. in Procedure
• Select the set data for Procedure
list of ceiling possible to be installed" table in this
manual.
Set data
Ceiling height
Code No.
Standard
0000
(Factory default)
0001
High ceiling (1)
0003
High ceiling (3)
Remote controller-less setting
] with [
]
Change the high-ceiling setting with the DIP switch on
the P.C. board.
* Once the Set data has been changed, though it can
]
be freely set to 0001 or 0003, to reset it to 0000
(factory default), it need changing using remote
controller (sold separately). After set data change,
an air conditioner is operated. After setting has been
completed, restart the air conditioner.
SW501-2
SW501-1
MCU
(IC501)
Set data
Ceiling height
Standard
0000
(Factory default)
0001
High ceiling (1)
0003
High ceiling (3)
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of Code No. [5d] to "0000".
7
).
4
.
5
from the "Height
SW501-1
SW501-2
OFF
OFF
ON
OFF
OFF
ON
228-EN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis