Page 31
p – band: [100 mV ]
4.4
The figure gives the proportional band ie the
regulation slope. The usual figure is 100 mV.
Meaning: For a p-band of 100 mV the dosing
pump works at full performance when the real
measured value deviates from the setpoint by 
100 mV. If the measured value within the p-
band approaches the reference value, the dosing
performance decreases proportionately. That is,
if the deviation is e.g.  50 mV the pump works
at only 50% of maximum performance.
4.5
I-reset time: [0 sec]
The default manufacturer's setting must not be
changed.
4.6
D-action time: [0 sec]
The default manufacturer's setting must not be
changed.

5. System settings

You can alter day, date, time, time delay at the
start-up and dosing time limit in the system set-
tings. Change from operating mode to set-up
mode by pressing the Mode key. Now press
the „Arrow up" key until "System set-up" ap-
pears in the display. Pressing the "OK" key
takes you back to the "Disinfection" sub-menu
"System settings".
When the option you want to change appears
in the display, press the "OK" key. A star ap-
pears in the display. The value can now be
changed using the arrow keys. To save the
changed value, press „OK" again. Cancel by
pressing the Mode key.

Time delay

2 min
Time delay *
2 min
4.7
Min. Output: [ 10 % ]
The control unit calculates the percentage dos-
ing performance of a given pump depending on
the deviation of the measuring of the setpoint.
A minimum output of e.g. 10% means that all
calculated values < 10% are automatically raised
to a minimum performance of 10%. That is, the
control unit works with a base load for small
deviations.
4.8
Max. Output: [ 100 %]
The control unit calculates the percentage dos-
ing performance of a given pump depending on
the deviation of the measuring of the setpoint.
A maximum output of e.g. 80% means that all
calculated values > 80% are automatically re-
duced to a maximum performance of 80%. This
reduces the dosing pump performance.

Dosing time (2)

120 min
Dosing time (1)
60 min
Time delay
8 min

Date

Tue 02.01.2022

Time

09:00
5.1 Time
You can set the current time in this menu item.
5.2 Date
You can set the current date in this menu item.
Sub-menu
You can scroll
through the sub
-menu by pres-
s i n g
t h e
„arrow" keys.