3. pH - value settings
The electrodes must be installed in the control
unit as shown in the above graphic
In the pH menu item, you can change all set-
tings necessary for pH control. Change from
operating mode to set-up mode by pressing the
Mode key. Now press the „arrow up" key until
"pH" appears in the display. Pressing the "OK"
key takes you back to the "pH" sub-menu for
pH control.
Operating mode
Stop
controller
pH
controller
SN6 - connec-
tion for pH
electrode
SN6 - connec-
tion for Rx
electrode
Thread for Rx
electrode
Thread for pH
electrode
.
Mode
OK
Calibration
pH

Setpoint (1)

7.20
Min. Alarm (1)
6.80
Max. Alarm (1)
7.60
P-band (1)
-1.00
I-reset time (1)
0 sec
D-action time (1)
0 sec
Min. Output (1)
10 %
Max. Output (1)
100%
When the option you want to change appears in
the display, press the "OK" key. A star appears
in the display. The value can now be changed
using the arrow keys. To save the changed value,
press „OK" again. Cancel by pressing the Mode
key.
Setpoint (1)
7.20
Sub-menu
You can
scroll
through the
sub-menu by
pressing the
„arrow" keys.
Setpoint (1)
*
7.20