RELAY OUTPUT FOR COOLING MODE INDICATION
There is the option for an external cooling mode indication
through the relay function via a potential-free switching
relay (max. 2 A) on the input board (AA2, terminal block X27).
If cooling mode indication is connected to terminal block
X27, it must be selected in menu 7.4.
DIP SWITCH
The DIP switch (S2) on the accessory board (AA5) must be
set as follows.
HPAC S40 | GB

Program settings

Program setting of HPAC S40 can be performed via the start
guide or directly in the menu system in your compatible heat
pump.
Caution
See also the Installer Manual for your compatible
heat pump.
START GUIDE
The start guide appears at first start-up after heat pump
installation, but can also be found in menu 7.7.
MENU SYSTEM
Settings can also be made in the menu system.
MENU 7.2.1 - ADD/REMOVE ACCESSORIES
Add or remove accessories here.
MENU 1.1 - TEMPERATURE
Here, you make temperature settings for your installation's
climate system.
MENU 1.1.2 - COOLING
Set the temperature (with room sensor
installed and activated):
Setting range: 5 – 35°C
The value in the display appears as a temperature in °C, if
the zone is controlled by a room sensor.
Caution
A slow climate system, such as underfloor heating,
may be unsuitable for controlling with room
sensors.
Setting the temperature (without room
sensors activated):
Setting range: -10 – 10
The display shows the set value for heating/cooling (curve
offset). To increase or reduce the indoor temperature, in-
crease or reduce the value in the display.
The number of steps the value has to be changed in order
to achieve a one degree change to the indoor temperature
depends on the climate system. One step is usually enough,
but in some cases several steps may be required.
If multiple zones in a climate system do not have activated
room sensors, these will have the same curve offset.
Setting the desired value. The new value is shown on the
right-hand side of the symbol on home screen cooling.
27