Program settings

Follow the instructions below to program the heat
pump for operation with PKM 05.
1. Start the heat pump.
2. Select "Service" in menu 8.1.1 to gain access to all
the menus.
3. Set the lowest permitted flow temperature to 18 °C
in menu 2.3. This is done to prevent condensation
precipitation. The factory setting is 15 °C.
4. Select PKM 05 (PKI) in menu 9.2.16. The factory set-
ting is "Off".
5. Select the cooling curve in menu 2.9.1. The factory
setting is 2.
Beräknad
Calculated
framledningstemp.
flow temperature
°C
20
15
10
5
0
0
20
6. Select the offset for the cooling curve in menu 2.9.2.
The factory setting is 0.
7. Select at which outdoor temperature the cooling
should start in the menu 2.9.3. The factory setting is
Beräknad framledningstemperatur
25 °C.
8. If RG 10 is fitted, the desired room temperature is
to be set using the RG 10 and menu 6.0. Cooling is
20
activated when the room temperature exceeds the
set temperature by the excess temperature selected in
menu 6.4 and when the condition in point 7 is met.
10
The cooling function is deactivated when the room
temperature drops by half the selected excess tempe-
rature.
0
20
30
NOTE!
To be able to obtain cooling mode, cooling
has to be activated in menu 2.9.5 or by
using the "Operating mode" button.
k=1
k=2
Outdoor
k=3
temp.
Utetemp.
°C
30
40
k = 1
k = 2
k = 3
40
Utetemperatur

Capacity diagram

Output
Effekt
kW
7,00
6,00
5,00
4,00
3,00
2,00
1,00
0,00
0
0,1
0,2
Pressure drop diagram
Pres. drop
Tryckfall
kPa
12
10
8
6
4
2
0
0
0,1
0,2
PKM 05
PKM 05
0,3
0,4
0,5
0,6
0,7
2
3
1
0,3
0,4
0,5
0,6
0,7
GB
Brine in 15°C
KBin 15 °C
VB in 21 °C
HW in 21°C
KB-flöde
Brine flow
l/s
1. Brine - No cooling
1. KB - Ej kylning
2. Brine - Cooling
2. KB - Kylning
3. VB
3. HW
Flow
Flöde
l/s
15

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis