Installation and Operating Instructions
EN
AMD – Medium-pressure axial fans
In particular, the inlet and outlet opening area must be protected by mounting extension ducts (for horizontal air flow
direction) or e.g. an on-site weather protection cover (end/beginning of a round/rectangular duct section for vertical
air flow direction).
The openings in the fan casing must be protected against the penetration of precipitation by a suitable installation
position (openings on side or below). In this respect, particular attention must be paid to the casing feed-through for
the supply line between the casing terminal box and motor connection.
3.3

Two-stage and parallel units

The various requirements concerning pressure increases, conveying capacities and space requirements are frequently
fulfilled by two-stage Z or parallel P units in the area of Technical Building Equipment (TGA). The Helios range (see sales
documents) offers corresponding mounting kits for the respective construction:
Two-stage design / mounting kit MP-Z
Two fans connected in series (Fig.11) ensure the
unrivalled power density and advantageous installa-
tion due to minimum space requirement.
The two fans are arranged in sequence and
connected with extension ducts.
m Vertical mounting ring is not possible (MRV)
Scope of delivery:
- Extension ducts (2 pcs.) incl. mounting kit
(hexagon head screws, nuts, spring washers).
Terminal box
MP-Z
Ø
A
B
C
Abmessungen:
315 317 356
381
1080
355 357 395
415
1206
400 402 438
471
1266
450 452 487
519
1416
500 502 541
570
1416
560 562 605
636
1960
630 632 674
719
2110
710 713 751
799
2110
800 801 837
897
2010
900 902 934
997
2190
1000 1001 1043 1097
2190
1120 1128 1174 1216
2460
3.4

Bearing condition diagnostics

Type: LZD-Basic and LZD-Comfort
The Helios bearing condition diagnostics system serves to securely monitor the functionality of motor bearings in
the drive motor of the smoke extraction fan. The system optionally allows the early detection of imminent bearing
damage by constantly or occasionally monitoring the bearing conditions. The bearings are not replaced periodically,
but depending on the actual wear. In this respect, the test and maintenance plan in these Installation and Operating
Instructions must be observed. Before operation and the use of bearing condition diagnostics, the separate Installation
and Operating Instructions for the monitoring system must be observed.
Information on other accessories can be found on the internet (www.heliosselect.de), TGA catalogue or the Helios
sales documentation.
Parallel unit / mounting kit MP-P
Two fans connected in parallel (Fig.12) provide
large air volumes with the corresponding pressure
rate and they meet the requirements for garage
ventilation and smoke extraction in particular.
Two identical fans arranged side by side work in
the same duct system.
Scope of delivery:
- Extension ducts (2 pcs.),
- Backdraught shutters (2 pcs.),
- Mounting brackets (4 pcs.)
- Mounting rails (2 pcs.)
- Mounting kits (hexagon head screws, nuts, spring
washers, washers and threaded plate).
Fig.11
MP-P
D
E
A
B
C
8x Ø 9.5
317 356 381
8x Ø9.5
357 395 415
12x Ø9.5
402 438 471
12x Ø9.5
452 487 519 1038 10
12x Ø9.5
502 541 570 1038 40
16x Ø11.5 562 605 636 1310 65
16x Ø 11.5 632 674 719 1455 115
16x Ø11.5 713 751 799 1455 155
24x Ø11.5 801 837 897 1425 200
24x Ø 11.5 902 934 997 1515 250 1018 1070-1240 2200 749 24x Ø 11.5
24x Ø11.5 1001 1043 1097 1515 300 1019 1200-1370 2400 814 24x Ø 11.5
24x Ø11.5 1128 1174 1216 1650 335 1154 1320-1380 2500 834 24x Ø 11.5
8
depending on accessories
D
E
F
G
1)
H
840
0
487
420-520 1085 316.5 8x Ø 9.5
903
0
550
460-580 1120 336
963
0
579,5
510-580 1120 346.5 12x Ø 9.5
654
560-650 1200 397 12x Ø 9.5
654
615-730 1500 445 12x Ø 9.5
925,5
700-820 1600 477 16x Ø 11.5
990
760-920 1700 527 16x Ø 11.5
980
860-1020 1900 639 16x Ø 11.5
928
950-1120 2000 689 24x Ø11.5
Fig.12
Terminal box
I
J
8x Ø 9.5