15 Commissioning software
Parameters
CO2 limit value max.
VOC limit value min.
VOC limit value max.
PPB 30 K relative hu-
midity limit value min.
(HPV)
PPB 30 K relative hu-
midity limit value max.
(IV)
EnOcean wireless
Parameters
Teaching mode
EnOcean unit list
Teach-out units
The PP 45 EO EnOcean module can only be
used in combination with the RLS 45 K control.
The activation of the PP 45 EO and the teach-
ing-in and teaching-out of radio components
and devices is only possible with the commis-
sioning software.
54
Set value
1000 ... 1200 ... 1500
ppm
500 ... 800 ... 900 ppm
1000 ... 1200 ... 1500
ppm
35 ... 40 ... 45 % r. h.
50 ... 70 ... 85 % r. h.
Set value
off, on
EEP list
15.6 Menu settings – Installer (only
for specialist installers)
NOTICE Incorrect settings can cause faults
and malfunctions.
Settings can only be undertaken at the installer
level by authorized installers specialised in ventil-
ation technology.
Password entry
After entering the password 6940, you are taken
to the installer level.
Exiting the installer level
1. Close Windows screen.
Installer level — standard display
Left side
• Current operating mode
• Current ventilation level
• Faults: visible when fault is present.
Right side
• Query: Shows current system values and sys-
tem statuses for the specialist installer.