15 Commissioning software
15.5 Menu settings — operator
Factory settings in bold
Basic settings
Ventilation
Sensors
EnOcean wireless
Installer
Basic settings
Parameters
Luminosity of LED in-
dicator
Luminosity of LED
standby
Set value
2, 3, 4, 5
0, 1, 2
Parameters
Time LED auto.
Standby
Ventilation
Parameters
Filter service life, unit
filter
Filter change, unit filter:
Acknowledgement
Duration of ventilation
level 5 (intermittent
ventilation)
Duration of night time
level 0 (sleep mode)
Sensors
Parameters
Relative humidity limit
value min. (HPV)
Relative humidity limit
value max. (IV)
CO2 limit value min.
Set value
0 ... 3 ... 6 minutes
Set value
1 ... 6 ... 8 months
changed, not changed
5 ... 30 ... 90 minutes
15 ... 60 ... 120 minutes
Set value
35 ... 35 ... 50 % r. h.
55 ... 60 ... 70 % r. h.
500 ... 800 ... 900 ppm