Connecting the DC cable to the DC switch
NOTE: For installation of the DC cables, use a torque wrench as well as the in-
cluded open-ended wrench for counter-resistance.
1 Pre-fit DC cable pair with the pre-installed screw and counternut onto the DC+
and DC busbar of the DC switch.
2 Option for 2 cable pairs: Insert spacer sleeve between 2 DC cables and pre-as-
semble in pairs with the provided screws and counternuts onto the DC+ and DC
busbar of the DC switch.
3 Slide the DC input plate up onto the housing base and secure. [
Nm ]
4 Secure the screws and counternuts onto the DC+ and DC busbar of the DC
switch. [
W_16/17] /
5 Tighten the cable screw fitting. [
» The device is connected to the PV generator.
4.5
Inserting the overvoltage protection
Information on the overvoltage protection: See
verter/manual" category.
4.6
Creating equipotential bonding
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second
ground connection. To this end, the threaded bolt on the underside of the device can be used.
↻ The device has been installed on the mount.
1 Strip the insulation from the equipotential bonding cable.
2 Furnish the stripped cable with an M8 ring cable lug.
3 Lay the cable for equipotential bonding onto the grounding point and attach
with an additional M8 nut and lock washer [
4 Check that the connected cable is fitted securely.
» The housing is included in the equipotential bonding.
4.7

Connecting the interfaces

4.7.1 Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death may result from improper use of the interface connections and failure to observe pro-
tection class III.
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with
protection class III.
All interfaces are located on the communication circuit board (HMI board) inside the housing.
Photovoltaic feed-in inverter - KACO blueplanet 87.0 - 165TL3
30 Nm ]
W_46 /
10 Nm ]
http://www.kaco-newenergy.com/de/downloads
W_17/
Option
T_30 /
6
Fig. 8: Fit DC cables to switch
1
Nut
2
Lock washer
3
Spacer sleeve
4
Fixing screw
10 Nm].
Fig. 9: Additional grounding point
1 Earthing bolt
1
2
4
1
2
3
4
in the "string in-
1
Page 9