Connecting the DC cable to the DC switch
NOTE: For installation of the DC cables, use a torque wrench as well as the in-
cluded open-ended wrench for counter-resistance.
1 Pre-fit DC cable pair with the pre-installed screw and counternut onto the DC+
and DC busbar of the DC switch.
2 Option for 2 cable pairs: Insert spacer sleeve between 2 DC cables and pre-as-
semble in pairs with the provided screws and counternuts onto the DC+ and DC
busbar of the DC switch.
3 Slide the DC input plate up onto the housing base and secure. [
53.10 In-Ibs ]
4 Secure the screws and counternuts onto the DC+ and DC busbar of the DC
switch. [
W_16/17] /
5 Tighten the cable screw fitting. [
» The device is connected to the PV generator.
4.5
Inserting the overvoltage protection
Information on the overvoltage protection: See
ual" category.
4.6
Creating equipotential bonding
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second
ground connection. To this end, the threaded bolt on the underside of the device can be used.
↻ The device has been installed on the mount.
1 Strip the insulation from the equipotential bonding cable.
2 Furnish the stripped cable with an M8 ring cable lug.
3 Place the earth cable at the earthing point and secure it with an additional M8
nut and lock washer [W_17/
4 Check that the connected cable is fitted securely.
» The housing is included in the equipotential bonding.
4.7
Connecting the interfaces
4.7.1 Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injuries or death may result from improper use of the interface connections and failure to observe
protection class III.
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with
protection class III.
All interfaces are located on the communication circuit board (HMI board) inside the housing.
Photovoltaik-feed-in inverter KACO blueplanet 87.0-165TL3
265.52 In-Ibs ]
W_46 /
88.50 In-Ibs ]
www.kaco-newenergy.com/de/downloads
88.5 In-Ibs ].
Option
T_30 /
Fig. 8: Fit DC cables to switch
1
Nut
2
Lock washer
3
Spacer sleeve
4
Fixing screw
in the "string inverter/man-
Fig. 9: Additional earthing point
1 Earthing bolt
1
2
4
1
2
3
4
1
Page 181