5

Configuration and operation

5.1
Controls
The 3 LEDs on the device show the different operating states. The LEDs can display the following states:
LED illuminated
Operating status
LED
Start
Feed-in start
Feed-in mode with re-
duced power
Non-grid feed mode
Error
6

Accessories

6.1
Inverter off
When using suitable KACO inverters, the shutdown can be carried out via the grid separation relay integrated into the
inverters and the "Inverter OFF" digital output instead of via interface switch.
Information about the "Inverter off" function: See manual under
"string inverter" category.
7

Maintenance and troubleshooting

Repairs may only be carried out by the authorised electrician.
Photovoltaic feed-in inverter - KACO blueplanet 87.0 - 165TL3
LED flashing
Icon
Description
The green "Operating" LED is illuminated when AC and DC voltage is
present.
If the LED is flashing, the internal communication between the compon-
ents is established. After flashing, the device is ready for feed-in.
If the LED continues to flash permanently, the internal communication is
interrupted.
The green "Operating" LED is lit.
The green "Feed-in" LED is illuminated after the country-specific wait-
ing period*.
The device feeds into the grid.
The interface switch engages audibly.
The green "Operating" LED is lit.
The green LED "Feed" is flashing because one of the modes: internal
power reduction, external power reduction, idle power request or stan-
dalone mode is active.
The device feeds into the grid.
The interface switch engages audibly.
The green "Operating" LED is lit.
None of the LEDs is illuminated or the red "Fault" LED is illuminated.
Error on AC/DC source
Conditional special cases:
ž
There is no DC voltage present (e.g. DC isolator switch open)
ž
DC voltage too low (< starting voltage)
DC voltage is present (> starting voltage), but communications connec-
tion between the front end (operating unit) and back end (control unit)
is faulty, or interrupted.
LED not illuminated