Herunterladen Inhalt Inhalt Diese Seite drucken

ABB ACH580-04 Kurzanleitung Für Die Installation Seite 14

Vorschau ausblenden Andere Handbücher für ACH580-04:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 23
14 EN – Quick installation guide (North America)
Default I/O connections
Default I/O connections of the HVAC default configuration are shown below.
1...10 kohm
Max.
USA
500 ohm
USA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
ZH
Digital inputs DI1...DI5 also support 10 to 24 V AC
Wire sizes: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
X1
Reference voltage and analog inputs and outputs
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
X2 & X3 Aux. voltage output and programmable digital inputs
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
Relay outputs
X6, X7, X8
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
30
A-
31
DGND
S4
TERM
S5
BIAS
X4
Safe torque off
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in Ext. 24V AC/DC input to power up the control unit
41
24 V AC/DC- in
2
(26...16 AWG): All terminals
Signal cable shield (screen)
Output frequency/speed reference: 0...10 V
Analog input circuit common
Reference voltage 10 V DC
!)
Actual feedback: 0...10 V
Analog input circuit common
Output frequency: 0...10 V
Motor current: 0...20 mA
Analog output circuit common
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
Stop (0) / Start (1)
Not configured
Constant frequency/speed selection
Start interlock 1 (1 = allow start)
Not configured
Not configured
Damper control
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
Embedded fieldbus, EFB (EIA-485)
Termination switch
Bias resistors switch
Safe torque off. Factory connection. Both
circuits must be closed for the drive to start. See
chapter Safe torque off function in ACH580-04
hardware manual (3AXD50000048685
[English]).
when the main supply is disconnected.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis