5. Confirmation of parts attached

This unit includes the following parts. Please check.
For usage methods, refer to item 10.2.
PQHY-P·YHM-A
1 Connecting pipe
IDø15.88, IDø19.05
(IDø5/8'', IDø3/4'')
<Gas side>
Model PQHY-P200YHM-A
1 pc.
PQHY-P250YHM-A
PQHY-P300YHM-A
PQRY-P·YHM-A
1 Connecting pipe
IDø15.88, IDø19.05
(IDø5/8'', IDø3/4'')
<High-pressure side>
Model PQRY-P200YHM-A
1 pc.
PQRY-P250YHM-A
PQRY-P300YHM-A

6. Lifting method

[Fig. 6.0.1] (P.2)
Use suspension ropes that will withstand the weight of the unit.
When moving the unit, use a 4-point suspension, and avoid giving impacts
to the unit (Do not use 2-point suspension).
Place protective pads on the unit where it comes in contact with the ropes to
protect the unit from being scratched.
Set the angle of roping at 40° or less.
Use 2 ropes that are each longer than 8 meters.
Place protective padding at the corners of the product to protect the product
from scratches or dents that might be caused by the rope.

7. Installation of unit

7.1. Installation

[Fig. 7.1.1] (P.2)
<A> Without detachable leg
M10 anchor bolt procured at the
A
site.
Check that the corner of the
C
installation leg is securely supported.
Fix unit tightly with bolts so that unit will not fall down due to earthquakes or
strong winds.
Use concrete or an angle bracket for the foundation of unit.
Vibration may be transmitted to the installation section and noise and
vibration may be generated from the floor and walls, depending on the
installation conditions. Therefore, provide ample vibrationproofing (cushion
pads, cushion frame, etc.).
Be sure that the corners are firmly seated. If the corners are not firmly
seated, the installation feet may be bent.
When using cushion pads, be sure that the full width of the unit is covered.
The projecting length of the anchor bolt should be less than 25 mm.
[Fig. 7.1.2] (P.2)
A Screws
The detachable leg can be removed at the site.
Detaching the detachable leg
Loosen the three screws to detach the detachable leg (Two each in the front
and back).
If the base leg finish is damaged when detaching, be sure to repair at the
site.
18
2 Connecting pipe
3 Connecting pipe
4 Connecting pipe
IDø19.05, IDø25.4
IDø22.2, IDø25.4
(IDø3/4'', ODø1'')
(IDø7/8'', IDø1'')
<Gas side>
<Gas side>
1 pc.
1 pc.
1 pc.
2 Connecting pipe
3 Connecting pipe
4 Connecting pipe
IDø19.05, IDø25.4
IDø22.2, IDø25.4
(IDø3/4'', ODø1'')
(IDø7/8'', IDø1'')
<High-pressure side>
<Low-pressure side>
<High-pressure side>
<Low-pressure side>
1 pc.
1 pc.
1 pc.
<B> With detachable leg
Check that the corner of the
B
installation leg is securely supported
to prevent the leg from bending.
Detachable leg
D
5 Water stopper
6 Water stopper
IDø9.52, IDø12.7
(large)
(IDø3/8'', IDø1/2'')
<Gas side>
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
5 Water stopper
6 Water stopper
IDø9.52, IDø12.7
(large)
(IDø3/8'', IDø1/2'')
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
Caution:
Be very careful when carrying/moving the product.
- When installing the heat source unit, suspend the unit at the specified location
of the unit base. Stabilize as necessary so that it does not move to the side
and support it at 4 points. If the unit is installed or suspended with 3-point
support, the unit may become unstable and fall.
Warning:
Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a
personal injury.
Have installation work in order to protect against strong winds and
earthquakes.
Any installation deficiency may cause unit to fall down, resulting in a
personal injury.
When building the foundation, give full attention to the floor strength, drain water
disposal <during operation, drain water flows out of the unit>, and piping and
wiring routes.
Precautions when routing the pipes and wires below the unit (Without
detachable leg)
When routing the pipes and wires below the unit, be sure that the foundation and
base work do not block the base through-holes. Also make sure the foundation
is at least 100 mm high so that the piping can pass under the unit.

7.2. Service space

Please allow for the following service spaces after installation.
In case of single installation, 600 mm or more of back space as front space
makes easier access when servicing the unit from rear side.
[Fig. 7.2.1] (P.3)
Space for removing the control box
A
Service space (front side)
C
7 Sealing material
8 Sealing material
(small)
(long)
(short)
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
7 Sealing material
8 Sealing material
(small)
(long)
(short)
1 pc.
1 pc.
1 pc.
Heat source unit
B
1 pc.
1 pc.
1 pc.

Werbung