Confirmation Of Parts Attached; Combination With Outdoor Units; Space Required Around Unit; Lifting Method - Mitsubishi Electric CITY MULTI PUHY-P-YEM-A Serie Installationshandbuch

Air-conditioners for building application outdoor unit
Inhaltsverzeichnis

Werbung

Super Y
Model
Noise level (50 / 60 Hz)
Constant capacity unit
Net weight
Variable capacity unit
Allowable pressure
External static pressure
Constant capacity unit
Refrigerant
Variable capacity unit
Total capacity
Indoor units
Model / Quantity
Operation temperature

3. Confirmation of parts attached

1 Conduit mounting plate (ø62) × 1
4 Tapping screw M4 × 4
6 Packing (inside ø29, outside ø39) × 1
1 Conduit mounting plate (ø40) × 1
4 Tapping screw M4 × 4
7 Packing (inside ø23, outside ø35) × 1

4. Combination with outdoor units

A Super Y (PUHY-P600/650/700/750YSEM-A) is produced when a Constant Ca-
pacity Unit (PUHN-P200/250YEM-A) is combined with this unit (PUHY-P400/
500YEM-A).
Use attachment parts 9 9 9 9 9 (Distributor kit) in constant capacity unit (PUHN-
P200/250YEM-A) when making a combination of these units.

5. Space required around unit

[Fig. 5.0.1] (P.2)
<A> Top view
<C> When there is little space up to an obstruction
A Front
B No restrictions on wall height (left and right)
C Air outlet guide (Procured at the site)
D Must be open
PUHN-P-YEM-A
PUHY-P-YEM-A
(1) Basic space required
A space of at least 250 mm is necessary at the back for inlet air. Taking servicing,
etc. from the rear into account, a space of about 450 mm should be provided, the
same as at the front.
(2) When there is an obstruction above the unit
(3) When inlet air enters from right and left sides of unit
Wall heights (H) of the front and the back sides shall be within overall height of
unit.
When the total height is exceeded, add the "h" dimension of the Fig. 5.0.1 to L
and L
.
2

6. Lifting method

[Fig. 6.0.1] (P.2)
Caution:
Be very careful when carrying the product.
- Do not have only one person to carry product if it weighs more than 20 kg.
- PP bands are used to pack some products. Do not use them as a mean for transportation because they are dangerous.
- Do not touch heat exchanger fins with your bare hands. Otherwise you cut your hands.
- Tear plastic packaging bag and scrap it so that children cannot play with it. Otherwise plastic packaging bag may suffocate children.
- When carrying outdoor unit, be sure to support it at four points. Carrying with 3-point support may make outdoor unit unstable, resulting in it falling.
12
PUHY-P600YSEM-A
61.5 / 62.0 dB <A>
248 kg
440 kg
R407C: 6.5 kg
R407C: 16 kg
Cooling mode: – 5 °CDB ~ 43 °CDB
Heating mode: – 15 °CWB ~ 15.5 °CWB (– 12 °CWB ~ 10 °CWB with indoor unit 20 or 25 type only is working.)
PUHY-P400/500YEM-A
Conduit mounting plate (ø53) × 1
2
Connecting pipe × 1 (Connecting pipe is fixed with the unit)
5
Wire mounting plate × 1
7
PUHN-P200/250YEM-A
Conduit mounting plate (ø33) × 1
2
Oil balance pipe 1 × 1
5
Seal × 2
8
<B> Side view
E Wall height (H)
L
L
1
2
450
250
450
450
PUHY-P650YSEM-A
PUHY-P700YSEM-A
62.0 / 62.5 dB <A>
61.5 / 62.0 dB <A>
263 kg
440 kg
HP: 2.94 MPa, LP: 1.6 MPa
0 MPa
R407C: 8.5 kg
R407C: 16 kg
50 ~ 130 %
20 ~ 250 / 2 ~ 32
(10 °CDB ~ 43 °CDB with outdoor unit at lower position, or with indoor unit
20 or 25 type only is working.)
Conduit mounting plate (ø46) × 1
3
Conduit mounting plate (ø27) × 1
3
Connecting pipe × 1 (Connecting pipe is fixed with the unit)
6
Distributor kit × 1
9
For R407 models
Super Y
PUHY-P600YSEM-A
PUHY-P650YSEM-A
PUHY-P700YSEM-A
PUHY-P750YSEM-A
(4) When unit is surrounded by walls
Note:
Wall heights (H) of the front and the back sides shall be within overall
height of unit.
If the panel height is exceeded, add the "h" dimension of the Fig. 5.0.1 to
L
and L
.
1
2
PUHN-P-YEM-A
PUHY-P-YEM-A
Example: When h is 100,
the L
dimension becomes 450 + 100 = 550 mm.
1
(5) Collective installation and continuous installation
Space required for collective installation and continuous installation:
When installing several units, leave the space between each block considering
passage for air and people.
Open in the two directions.
In case wall height (H) exceeds overall height of unit, add "h" dimension (h =
wall height <H> – overall height of unit) to * marked dimension.
If there is a wall at both the front and the rear of the unit, install up to three units
1
consecutively in the side direction and provide a space of 1000 mm or more as
inlet space/passage space for each three units.
PUHY-P750YSEM-A
62.0 / 62.5 dB <A>
248 kg
263 kg
475 kg
475 kg
R407C: 6.5 kg
R407C: 8.5 kg
R407C: 21 kg
R407C: 21 kg
Variable capacity unit
Constant capacity unit
PUHN-P200YEM-A
PUHY-P400YEM-A
PUHN-P250YEM-A
PUHN-P200YEM-A
PUHY-P500YEM-A
PUHN-P250YEM-A
L
1
450
450
L
2
250
450