2. About the product

This unit uses R410A-type refrigerant.
Piping for systems using R410A may be different from that for systems using
conventional refrigerant because the design pressure in systems using R410A
is higher. Refer to the Data Book for more information.
Some of the tools and equipment used for installation with systems that use
other types of refrigerant cannot be used with the systems using R410A. Refer
to the Data Book for more information.
Do not use the existing piping, as it contains chlorine, which is found in con-
ventional refrigerating machine oil and refrigerant. This chlorine will deteriorate
the refrigerant machine oil in the new equipment. The existing piping must not
be used as the design pressure in systems using R410A is higher than that in
the systems using other types of refrigerant and the existing pipes may burst.

3. Combination of outdoor units

Component units of PUHY-HP400 to HP500 are listed below.
Outdoor unit model
PUHY-HP200YHM-A(-BS)
PUHY-HP250YHM-A(-BS)
PUHY-HP400YSHM-A(-BS)
PUHY-HP500YSHM-A(-BS)
* PUHY-HP400/500YSHMC-A(-BS) require "Twinning Kit" to connect component unit modules in the field.

4. Specifications

Model
Sound level (60Hz)
External static pressure
Total capacity
Indoor units
Model
Quantity
Standard type
Cooling mode: – 5°CDB ~ 43°CDB (0°CDB ~ 43°CDB with outdoor unit at lower position)
Operation
Heating mode: – 25°CWB ~ 15.5°CWB
temperature
Outside air
Cooling mode: 21°CDB/15.5°CWB ~ 43°CDB/35°CWB
intake type
Heating mode: – 10°CDB ~ 20°CDB
*1: The total indoor capacity of units run simultaneously is 130% or less.
*2: To enable high static pressure, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON

5. Confirmation of parts attached

This unit includes the following parts. Please check.
For usage methods, refer to item 10.2.
1 Connecting elbow (brazed)
<Gas side>
P200
Model
P250

6. Space required around unit

1 In case of single installation
Secure enough space around the unit as shown in the figure on page 2.
[Fig. 6.0.1] (P.2)
<A> Top view
<C> When there is little space up to an obstruction
A Front
B Unit height
C Back
D Air outlet guide (Procured at the site)
(1) If the distance is 300 mm or more between the rear side and the wall
(2) If the distance is 100 mm or more between the rear side and the wall
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defined here, add the height that exceeds the height
limit <h> to the figures that are marked with an asterisk.
12
Component unit models
-
-
PUHY-HP200YHM-A(-BS)
PUHY-HP250YHM-A(-BS)
PUHY-HP200YHM-A
PUHY-HP250YHM-A
56dB <A>
1 ~ 17
2 Connecting pipe (brazed)
<Gas side>
1 pc.
1 pc.
-
1 pc.
<B> Side view
Caution:
Do not vent R410A into the atmosphere.
R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol
with a Global Warming Potential (GWP) = 1975.
-
-
PUHY-HP200YHM-A(-BS)
PUHY-HP250YHM-A(-BS)
PUHY-HP400YSHM-A
59dB <A>
57dB <A>
0 Pa*
2
50 ~ 130%*
1
15 ~ 250
1 ~ 21
3 Connecting pipe (brazed)
<Gas side>
-
1 pc.
<Wall height limit> Front: Up to the unit height
(4) If there are obstacles at the upper part of the unit
2 In case of collective installation
[Fig. 6.0.2] (P.2)
A Front
C Wall height (H)
When multiple units are installed adjacent to each other, secure enough space
to allow for air circulation and walkway between groups of units as shown in
the figures on page 2.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk.
PUHY-HP500YSHM-A
60dB <A>
1 ~ 34
1 ~ 43
4 Connecting pipe (brazed)
5 Connecting pipe (brazed)
<Liquid side>
1 pc.
1 pc.
Back: Up to 500 mm from the unit bottom
Side: Up to the unit height
B Must be open
<Liquid side>
1 pc.
1 pc.