5

Transport

A lift truck is suited for transporting the unit on a level surface.
Carrying straps may be used if the heat pump needs to be trans-
ported on an uneven surface or carried up or down stairs. These
straps can be passed directly underneath the pallet.
ATTENTION!
The heat pump is not secured to the pallet.
ATTENTION!
The heat pump must not be tilted more than 45° (in any direction).
Use the holes provided in the sides of the frame to lift the unit
without the pallet. The side panel assemblies must be removed
for this purpose. Any commercially available length of pipe can
be used as a carrying aid.
ATTENTION!
Do not use the holes in the panel assemblies for lifting the device!)
www.dimplex.de
6

Set-up

6.1 General Information

The brine-to-water heat pump must be installed in a frost-free,
dry room on an even, smooth and horizontal surface. The entire
base of the frame should lie directly on the floor to ensure a ade-
quate soundproof seal. If this is not the case, additional sound in-
sulation measures may be necessary.
The heat pump must be installed so that maintenance work can
be carried out without hindrance. This can be ensured by main-
taining a clearance of approx. 1 m in front of and on each side of
the heat pump.
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.

6.2 Attaching the heat pume

If the heat pump is set up in areas at risk from earthquakes, there
is the option of screwing the heat pump to the subsurface. Rele-
vant notches are present in the heat pump holder
The holes in the subsurface must be drilled before setting up the
heat pump. The positions of the holes are shown in the dimen-
sion drawing (see Cap. 1 on pag. II).

6.3 Acoustic Emissions

The heat pump operates silently due to efficient sound insulation.
To prevent noise transmission to the foundation, a suitable,
sound dampening rubber mat should be placed underneath the
base frame of the heat pump.
To prevent any sound from being transmitted to the heating sys-
tem, we recommend connecting the heat pump to the heating
system by means of hose sections.
452232.66.35 · FD 9311